A05VVR 3G10 #D
A05VVR 3G10 #D
A05VVR 3G10 #D
Read more- Nexans ref. : 13001097
- Country ref. : 13001097
- EAN : 5204609010971
Description
Description
Standards
-
TestIEC 60332-1
-
InternationalHD 21.4
-
NationalELOT 563.4
Design
Copper cable with solid or stranded copper conductor suitable for installation in dry or wet places.
Design
- Copper conductor
- PVC Insulation
- PVC Outer sheath
Note: U: solid conductor, R: round stranded conductor
Insulation colors
2-cores: Brown, Blue
3-cores: Brown, Yellow-green, Blue
4-cores: Brwon, Black, Grey, Yellow-green
5-cores: Brown, Black, Grey, Yellow-green, Blue
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor shape
Round, stranded
Conductor flexibility
Stranded class 2
Insulation
PVC
Outer sheath
PVC
Sheath colour
White
Type of conductor
R
With Green/Yellow core
Yes
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Number of cores
3
Approximate weight
520 kg/km
Conductor cross-section
10 mm²
Phase Conductor Cross Section
10 mm²
Ground conductor cross-section
10 mm²
Wire section
- mm²
Nominal insulation thickness
1.0 mm
Nominal outer sheath thickness
1.4 mm
Nominal outer diameter
17.0 mm
Neutral conductor section (when smaller)
- mm²
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
300/500 V
Max. DC resistance of the conductor at 20°C
1.83 Ohm/km
Maximum permissible nominal current
65 A
Voltage drop, single phase
4.4 V/A.km
Voltage drop, 3 conductors
3.8 V/A.km
Resources
Resources
Current capacity table PVC insulation single core three phase
PVC insulation/three loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A1 Insulated conductors in conduit in a thermally insulated wall | B1 Insulated conductors in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | F Single-core flat cables, touching in free air | F Single-core trefoil cables, touching in free air | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 10.0 |
A1 Insulated conductors in conduit in a thermally insulated wall
42.0 |
B1 Insulated conductors in conduit on a wooden wall
32.0 |
C Single-core or multi-core cable on a wooden wall
50.0 |
D1 Single-core or Multi-core cable in ducts in the ground
39.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
57.0 |
F Single-core flat cables, touching in free air
44.0 |
F Single-core trefoil cables, touching in free air
50.0 |
mm² 39.0 |
Cu 54.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Current capacity table PVC insulation multicore three phase
PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A2 Multi-core cable in conduit in a thermally insulated wall | B2 Multi-core cable in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | E Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 10.0 |
A2 Multi-core cable in conduit in a thermally insulated wall
39.0 |
B2 Multi-core cable in conduit on a wooden wall
31.0 |
C Single-core or multi-core cable on a wooden wall
46.0 |
D1 Single-core or Multi-core cable in ducts in the ground
36.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
57.0 |
E Multi-core cable in free air
44.0 |
mm² 50.0 |
Cu 39.0 |
Al 54.0 |
Cu 0.0 |
Al 60.0 |
Cu 46.0 |
Current capacity table PVC insulation multicore single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A2 Multi-core cable in conduit in a thermally insulated wall | B2 Multi-core cable in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | E Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 10.0 |
A2 Multi-core cable in conduit in a thermally insulated wall
43.0 |
B2 Multi-core cable in conduit on a wooden wall
33.0 |
C Single-core or multi-core cable on a wooden wall
52.0 |
D1 Single-core or Multi-core cable in ducts in the ground
41.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
63.0 |
E Multi-core cable in free air
49.0 |
mm² 60.0 |
Cu 47.0 |
Al 64.0 |
Cu 0.0 |
Al 70.0 |
Cu 54.0 |
Current capacity table PVC insulation single core single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A1 Insulated conductors in conduit in a thermally insulated wall | B1 Insulated conductors in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | F Single-core flat cables, touching in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 10.0 |
A1 Insulated conductors in conduit in a thermally insulated wall
46.0 |
B1 Insulated conductors in conduit on a wooden wall
36.0 |
C Single-core or multi-core cable on a wooden wall
57.0 |
D1 Single-core or Multi-core cable in ducts in the ground
44.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
63.0 |
F Single-core flat cables, touching in free air
49.0 |
mm² 60.0 |
Cu 47.0 |
Al 64.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Declaration of Performance
- Declaration of Performance n� : 1000423-GRLA
- Certification Date : 7/3/17
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 0832
- Declared performance : Eca