A05VVU 4G 4 #D

Description

Description

Standards

  • International
    HD 21.4; IEC 60332-1
  • National
    ELOT 563.4

Copper cable with solid or stranded copper conductor suitable for installation in dry or wet places.

 

Design

  1. Copper conductor
  2. PVC Insulation
  3. PVC Outer sheath

 

Core marking

2-cores: Brown, Blue

3-cores: Brown, Yellow-green, Blue

4-cores: Brwon, Black, Grey, Yellow-green

5-cores: Brown, Black, Grey, Yellow-green, Blue

 

Cable construction

1. copper conductor

2. PVC insulation

3. PVC outer sheath

 Note: upon request the cable could be manufactured with higher fire retardant performance to meet the standards BS/EN 50266 cat C, IEC 60332-3-24 cat C

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Round, massive
Conductor flexibility
Solid class 1
Insulation
PVC
Outer sheath
PVC
Sheath colour
White
Type of conductor
U
With Green/Yellow core
Yes
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Approximate weight
310 kg/km
Conductor cross-section
4 mm²
Phase Conductor Cross Section
4 mm²
Ground conductor cross-section
4 mm²
Wire section
- mm²
Nominal insulation thickness
0.8 mm
Nominal outer sheath thickness
1.2 mm
Nominal outer diameter
12.5 mm
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
300/500 V
Max. DC resistance of the conductor at 20°C
4.61 Ohm/km
Maximum permissible nominal current
36 A
Voltage drop, single phase
- V/A.km
Voltage drop, 3 conductors
9.5 V/A.km

Resources

Resources

Current capacity table PVC insulation single core three phase

PVC insulation/three loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air F Single-core trefoil cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 24.0 18.5 28.0 22.0 32.0 25.0 30.0 24.0 33.0 0.0 0.0 0.0 0.0 0.0

Current capacity table PVC insulation multicore three phase

PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A2 Multi-core cable in conduit in a thermally insulated wall B2 Multi-core cable in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground E Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 23.0 17.5 27.0 21.0 32.0 25.0 30.0 24.0 33.0 0.0 34.0 26.0

Current capacity table PVC insulation multicore single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A2 Multi-core cable in conduit in a thermally insulated wall B2 Multi-core cable in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground E Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 25.0 19.5 30.0 24.0 36.0 28.0 37.0 29.0 38.0 0.0 40.0 31.0

Current capacity table PVC insulation single core single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 26.0 20.0 32.0 25.0 36.0 28.0 37.0 29.0 38.0 0.0 0.0 0.0

Selling & delivery Information

Note: U: solid conductor, R: round stranded conductor

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close