H05VVF 4G 4 #C

Description

Description

Standards

  • Product
    EN 50525-2-11; HD 21.5
  • Test
    IEC 60332-1-2
  • National
    ELOT 563.5

Application and design

Copper flexible cable suitable for indoor installation in pipes or trays

 

1. Flexible copper conductor

2. PVC insulation

3. PVC sheath

Insulation colors

2-cores: Brown, Blue

3-cores: brown, Yellow-green, Blue

4-cores: Brown, Black, Grey, yellow-green

5-cores: Brown, Black, Grey, Yellow-green, Blue

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor flexibility
Flexible class 5
Conductor shape
Circular
Insulation
PVC
Outer sheath
PVC
Sheath colour
White
With Green/Yellow core
Yes
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Conductor cross-section
4 mm²
Phase Conductor Cross Section
4 mm²
Ground conductor cross-section
4 mm²
Nominal insulation thickness
0.8 mm
Nominal outer sheath thickness
1.2 mm
Nominal outer diameter
12.8 mm
Approximate weight
275 kg/km
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
300/500 V
Max. DC resistance of the conductor at 20°C
4.95 Ohm/km
Maximum permissible nominal current
36 A
Voltage Drop
10.0 V/A.km

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Flexible

Resources

Resources

Current capacity table PVC insulation single core three phase

PVC insulation/three loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air F Single-core trefoil cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 24.0 18.5 28.0 22.0 32.0 25.0 30.0 24.0 33.0 0.0 0.0 0.0 0.0 0.0

Current capacity table PVC insulation multicore three phase

PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A2 Multi-core cable in conduit in a thermally insulated wall B2 Multi-core cable in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground E Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 23.0 17.5 27.0 21.0 32.0 25.0 30.0 24.0 33.0 0.0 34.0 26.0

Current capacity table PVC insulation single core single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 26.0 20.0 32.0 25.0 36.0 28.0 37.0 29.0 38.0 0.0 0.0 0.0

Current capacity table PVC insulation multicore single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A2 Multi-core cable in conduit in a thermally insulated wall B2 Multi-core cable in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground E Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 25.0 19.5 30.0 24.0 36.0 28.0 37.0 29.0 38.0 0.0 40.0 31.0

Declaration of Performance

  • Declaration of Performance n� : 1000492-GRLA
  • Certification Date : 7/3/17
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0051
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close