H05VVF 5G 1.5 #C
H05VVF 5G 1.5 #C
H05VVF 5G 1.5 #C
Read more- Nexans ref. : 13001546
- Country ref. : 13001546
- EAN : 5204609015358
Description
Description
Standards
-
ProductEN 50525-2-11; HD 21.5
-
TestIEC 60332-1-2
-
NationalELOT 563.5
Application and design
Copper flexible cable suitable for indoor installation in pipes or trays
1. Flexible copper conductor
2. PVC insulation
3. PVC sheath
Insulation colors
2-cores: Brown, Blue
3-cores: brown, Yellow-green, Blue
4-cores: Brown, Black, Grey, yellow-green
5-cores: Brown, Black, Grey, Yellow-green, Blue
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor flexibility
Flexible class 5
Conductor shape
Circular
Insulation
PVC
Outer sheath
PVC
Sheath colour
White
With Green/Yellow core
Yes
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Number of cores
5
Conductor cross-section
1.5 mm²
Phase Conductor Cross Section
1.5 mm²
Ground conductor cross-section
1.5 mm²
Nominal insulation thickness
0.7 mm
Nominal outer sheath thickness
1.1 mm
Nominal outer diameter
10.5 mm
Approximate weight
160 kg/km
Neutral conductor section (when smaller)
- mm²
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
300/500 V
Max. DC resistance of the conductor at 20°C
13.3 Ohm/km
Maximum permissible nominal current
20 A
Voltage Drop
28.0 V/A.km
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Flexible
Resources
Resources
Current capacity table PVC insulation single core three phase
PVC insulation/three loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A1 Insulated conductors in conduit in a thermally insulated wall | B1 Insulated conductors in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | F Single-core flat cables, touching in free air | F Single-core trefoil cables, touching in free air | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 1.5 |
A1 Insulated conductors in conduit in a thermally insulated wall
13.5 |
B1 Insulated conductors in conduit on a wooden wall
0.0 |
C Single-core or multi-core cable on a wooden wall
15.5 |
D1 Single-core or Multi-core cable in ducts in the ground
0.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
17.5 |
F Single-core flat cables, touching in free air
0.0 |
F Single-core trefoil cables, touching in free air
18.0 |
mm² 0.0 |
Cu 19.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Current capacity table PVC insulation multicore three phase
PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A2 Multi-core cable in conduit in a thermally insulated wall | B2 Multi-core cable in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | E Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 1.5 |
A2 Multi-core cable in conduit in a thermally insulated wall
13.0 |
B2 Multi-core cable in conduit on a wooden wall
0.0 |
C Single-core or multi-core cable on a wooden wall
15.0 |
D1 Single-core or Multi-core cable in ducts in the ground
0.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
17.5 |
E Multi-core cable in free air
0.0 |
mm² 18.0 |
Cu 0.0 |
Al 19.0 |
Cu 0.0 |
Al 18.5 |
Cu 0.0 |
Current capacity table PVC insulation single core single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A1 Insulated conductors in conduit in a thermally insulated wall | B1 Insulated conductors in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | F Single-core flat cables, touching in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 1.5 |
A1 Insulated conductors in conduit in a thermally insulated wall
14.5 |
B1 Insulated conductors in conduit on a wooden wall
0.0 |
C Single-core or multi-core cable on a wooden wall
17.5 |
D1 Single-core or Multi-core cable in ducts in the ground
0.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
19.5 |
F Single-core flat cables, touching in free air
0.0 |
mm² 22.0 |
Cu 0.0 |
Al 22.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Current capacity table PVC insulation multicore single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A2 Multi-core cable in conduit in a thermally insulated wall | B2 Multi-core cable in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | E Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 1.5 |
A2 Multi-core cable in conduit in a thermally insulated wall
14.0 |
B2 Multi-core cable in conduit on a wooden wall
0.0 |
C Single-core or multi-core cable on a wooden wall
16.5 |
D1 Single-core or Multi-core cable in ducts in the ground
0.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
19.5 |
E Multi-core cable in free air
0.0 |
mm² 22.0 |
Cu 0.0 |
Al 22.0 |
Cu 0.0 |
Al 22.0 |
Cu 0.0 |
Declaration of Performance
- Declaration of Performance n� : 1000492-GRLA
- Certification Date : 7/3/17
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 0051
- Declared performance : Eca
Our websites