H07VR 1X 35 BR #D

Description

Description

Standards

  • Product
    BS 6004; EN 50525-2-31; HD 21.3; IEC 60227-1
  • National
    ELOT 563.3

Single core non-sheathed power cable with copper conductor and PVC insulation suitable for rated voltages 450/750V

 

Application

H07V-U and H07V-R are used for fixed protected installations in, or on, lighting or controlgear...

 

Installation

In cable dusts, in trunks or in cable conduits

 

Colours

Black, Brown, Blue, Yellow-green

Note: on request the cables are available in other colours such as: Red, Grey, Orange, White,...

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Type of conductor
R
Conductor flexibility
Stranded class 2
Conductor shape
Circular
Insulation
PVC
Colour
Brown
Lead free
Yes
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
35 mm²
Phase Conductor Cross Section
35 mm²
Nominal insulation thickness
1.2 mm
Nominal outer diameter
11.4 mm
Approximate weight
350 kg/km
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Max. DC resistance of the conductor at 20°C
0.524 Ohm/km
Maximum permissible nominal current
110 A
Voltage drop, single phase
1.25 V/A.km
Voltage drop, 3 conductors
1.1 V/A.km

Usage characteristics

Usage characteristics

Operating temperature, range
-5 ... 60 °C
Max. conductor temperature in service
70 °C
Short-circuit max. conductor temperature
160 °C

Resources

Resources

Current capacity table PVC insulation single core single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
35.0 99.0 77.0 125.0 97.0 138.0 103.0 119.0 93.0 132.0 98.0 162.0 122.0

Current capacity table PVC insulation single core three phase

PVC insulation/three loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air F Single-core trefoil cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
35.0 89.0 70.0 110.0 86.0 119.0 90.0 98.0 77.0 110.0 83.0 143.0 109.0 137.0 105.0

Selling & delivery Information

Type conductor: U (solid, class 1) or R (circular stranded, class 2)

Declaration of Performance

  • Declaration of Performance n� : 1000425-GRLA
  • Certification Date : 7/3/17
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0832
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*