ruNeasy H07V-R 6 mm2 BR #C

Description

Description

Standards

  • Product
    BS 6004; EN 50525-2-31; HD 21.3; IEC 60227-1
  • National
    ELOT 563.3

Single core non-sheathed power cable with copper conductor and PVC insulation suitable for rated voltages 450/750V

 

Application

H07V-U and H07V-R are used for fixed protected installations in, or on, lighting or controlgear... 

 

Installation

In cable dusts, in trunks or in cable conduits. The installation time of the cable inside the plastic tubes is reduced in relation of the similar cables due to the lower friction. 

 

Colours

Black, Brown, Blue, Grey, Yellow-green, Red, White

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Type of conductor
R
Conductor flexibility
Stranded class 2
Conductor shape
Circular
Insulation
PVC
Colour
Brown
Lead free
Yes
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
6 mm²
Phase Conductor Cross Section
6 mm²
Nominal insulation thickness
0.8 mm
Nominal outer diameter
5.2 mm
Approximate weight
65 kg/km
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Max. DC resistance of the conductor at 20°C
3.08 Ohm/km
Maximum permissible nominal current
35 A
Voltage drop, single phase
7.3 V/A.km
Voltage drop, 3 conductors
6.4 V/A.km

Usage characteristics

Usage characteristics

Operating temperature, range
-5 ... 60 °C
Max. conductor temperature in service
70 °C
Short-circuit max. conductor temperature
160 °C

Resources

Resources

Current capacity table PVC insulation single core single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
6.0 34.0 26.0 41.0 32.0 46.0 36.0 46.0 36.0 48.0 0.0 0.0 0.0

Current capacity table PVC insulation single core three phase

PVC insulation/three loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air F Single-core trefoil cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
6.0 31.0 24.0 36.0 28.0 41.0 32.0 38.0 30.0 41.0 0.0 0.0 0.0 0.0 0.0

Declaration of Performance

  • Declaration of Performance n� : 1001106-GRLA
  • Certification Date : 8/31/22
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0832
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close