R2V 1X 95 C #D
R2V 1X 95 C #D
R2V 1X 95 C #D
Read more- Nexans ref. : 13000315
- Country ref. : 13000315
- EAN : 5204609003157
Description
Description
Standards
-
ProductIEC 60502-1; NF C32-321
-
TestIEC 60332-1
Application
Electric cable with copper solid or stranded conductors with XLPE insulation and PVC outer sheath.
The cable is suitable for fixed installations, indoor and outdoor.
According to CPR regulation the cable is Euroclass Eca
Construction
1. copper conductor
2. XLPE insulation
3. PVC outer sheath
Note: U:circular solid conductor, R:circular stranded conductor, S:sector-shaped stranded conductor
Note: upon request the cable could be available with higher fire retardant performance to meet the standard IEC 60322-3-24 cat C
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor shape
Circular
Type of conductor
Class 2
Conductor flexibility
Stranded class 2
Insulation
XLPE
Outer sheath
PVC
Sheath colour
Black
Lead free
Yes
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Conductor cross-section
95 mm²
Phase Conductor Cross Section
95 mm²
Nominal insulation thickness
1.1 mm
Nominal outer sheath thickness
1.5 mm
Nominal outer diameter
16.5 mm
Approximate weight
930 kg/km
Neutral conductor section (when smaller)
- mm²
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Max. DC resistance of the conductor at 20°C
0.193 Ohm/km
Permissible current rating when buried
301 A
Permissible current rating in open air
328 A
Voltage drop, 3 conductors
0.43 V/A.km
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Mechanical resistance to impacts
Good
Usage characteristics
Usage characteristics
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Weather resistance
Yes
Resources
Resources
Current capacity table XLPE insulation single core three phase
XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A1 Insulated conductors in conduit in a thermally insulated wall | B1 Insulated conductors in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | F Single-core flat cables, touching in free air | F Single-core trefoil cables, touching in free air | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 95.0 |
A1 Insulated conductors in conduit in a thermally insulated wall
216.0 |
B1 Insulated conductors in conduit on a wooden wall
171.0 |
C Single-core or multi-core cable on a wooden wall
269.0 |
D1 Single-core or Multi-core cable in ducts in the ground
217.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
278.0 |
F Single-core flat cables, touching in free air
211.0 |
F Single-core trefoil cables, touching in free air
197.0 |
mm² 154.0 |
Cu 226.0 |
Al 172.0 |
Cu 342.0 |
Al 264.0 |
Cu 328.0 |
Al 253.0 |
Current capacity table XLPE insulation single core single phase
XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | A1 Insulated conductors in conduit in a thermally insulated wall | B1 Insulated conductors in conduit on a wooden wall | C Single-core or multi-core cable on a wooden wall | D1 Single-core or Multi-core cable in ducts in the ground | D2 Single-core or Multi-core cables designed to be buried directly in the ground | F Single-core flat cables, touching in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 95.0 |
A1 Insulated conductors in conduit in a thermally insulated wall
241.0 |
B1 Insulated conductors in conduit on a wooden wall
191.0 |
C Single-core or multi-core cable on a wooden wall
306.0 |
D1 Single-core or Multi-core cable in ducts in the ground
242.0 |
D2 Single-core or Multi-core cables designed to be buried directly in the ground
328.0 |
F Single-core flat cables, touching in free air
241.0 |
mm² 239.0 |
Cu 186.0 |
Al 270.0 |
Cu 204.0 |
Al 377.0 |
Cu 289.0 |
Declaration of Performance
- Declaration of Performance n� : 1000430-GRLA
- Certification Date : 7/3/17
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 0832
- Declared performance : Eca