CONCENTRIC 4X 6 #C #N

Description

Description

Standards

  • Product
    HD 626-10N
  • National
    DEH KK 03.02

Appllication

Electric cable with copper conductors and concentric neutral conductor.

The cable is suitable for outdoor installation on poles.

According to CPR regulation the cable is Euroclass Eca.

Construction

The cable is consisted of stranded tinned copper phase conductor (-s), EPR insulation, tinned copper with for neutral concentric conductor, elastomer outer sheath.

The insulation colors are according to HD 308.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor shape
Circular
Conductor material
Tinned copper
Insulation
EPR
Concentric conductor
Tinned copper wires
Outer sheath
Elastomer
Colour
Black
Lead free
Yes
Conductor flexibility
Stranded class 2
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
6 mm²
Number of phases
3
Nominal outer diameter
17.5 mm
Approximate weight
500 kg/km
Neutral conductor section (when smaller)
- mm²
Number of cores
4

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
1.16 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Resources

Resources

Current capacity table PVC insulation multicore three phase

PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A2 Multi-core cable in conduit in a thermally insulated wall B2 Multi-core cable in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground E Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
6.0 29.0 23.0 34.0 27.0 41.0 32.0 38.0 30.0 41.0 0.0 43.0 33.0

Current capacity table PVC insulation multicore single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A2 Multi-core cable in conduit in a thermally insulated wall B2 Multi-core cable in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground E Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
6.0 32.0 25.0 38.0 30.0 46.0 36.0 46.0 36.0 48.0 0.0 51.0 39.0

Declaration of Performance

  • Declaration of Performance n� : 1000820-GRLA
  • Certification Date : 3/12/19
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0832
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close