CU/EPR/PCP 01 1X 4 U TIN YG #C

Description

Description

Standards

  • Product
    HD 626-9N; IEC 60502-1
  • National
    DEH KK 03.05

Application

Power cable for outdoor and indoor installation, in air on trays.

According to CPR regulation the cable is Euroclass Eca

Construction

The cable is consisted of circular Tinned copper conductor, EPR insulation and elastomer outer sheath

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Tinned copper
Conductor shape
Circular
Conductor flexibility
Solid class 1
Insulation
EPR
Colour
Yellow / green
Outer sheath
Elastomer
Sheath colour
Black
Lead free
Yes
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
4 mm²
Phase Conductor Cross Section
- mm²
Nominal insulation thickness
1.0 mm
Nominal outer sheath thickness
1.4 mm
Nominal outer diameter
7.1 mm
Approximate weight
86 kg/km
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
4.7 Ohm/km
Permissible current rating in open air
44 A

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2

Resources

Resources

Current capacity table PVC insulation single core single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 26.0 20.0 32.0 25.0 36.0 28.0 37.0 29.0 38.0 0.0 0.0 0.0

Current capacity table PVC insulation single core three phase

PVC insulation/three loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air F Single-core trefoil cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4.0 24.0 18.5 28.0 22.0 32.0 25.0 30.0 24.0 33.0 0.0 0.0 0.0 0.0 0.0

Declaration of Performance

  • Declaration of Performance n� : 1000819-GRLA
  • Certification Date : 3/12/19
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0832
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close